Ventilation perturbations due to an open fireplace in a house
TitelVentilation perturbations due to an open fireplace in a house
Verantwoordelijkheids-vermeldingP. Dalicieux, C. Nicolas
Verantwoordelijke(n)
Jaar van uitgave1990
Materiaalartikel
SamenvattingNowadays in France, new housing is very well insulated. The installation of an open fireplace can considerably lower this insulation due to the increase of air change.
With the help of a building thermal simulation model including the calculation of the air flow rates through the building shell, the ventilation system and flue, we shall evaluate the overconsumption risks due to the presence of the chimmey.
In the example presented here, the annual heating consumption is increased by 30% within a non-lit open fireplace where the flue gate (damper) remained open compared with the same house without a chimney. Moreover, for a —6 °C outdoor temperature the power demand is increased by 1.5 kW.
With the help of a building thermal simulation model including the calculation of the air flow rates through the building shell, the ventilation system and flue, we shall evaluate the overconsumption risks due to the presence of the chimmey.
In the example presented here, the annual heating consumption is increased by 30% within a non-lit open fireplace where the flue gate (damper) remained open compared with the same house without a chimney. Moreover, for a —6 °C outdoor temperature the power demand is increased by 1.5 kW.
AnnotatieIn: Energy and Buildings, Volume 14, Issue 3, November 1990.- pagina's 211-214
ISSN: 0378-7788
Met literatuuropgave
ISSN: 0378-7788
Met literatuuropgave
Trefwoordenhaarden, Haardvuur, Open haard, ventilatie, binnenklimaat, volksgezondheid