From design to reality : optimizing energy use and climate conditions in the CC NL shared storage facility
TitelFrom design to reality : optimizing energy use and climate conditions in the CC NL shared storage facility
Verantwoordelijkheids-vermeldingBart Ankersmit, Gerrit Engberts, Wim Hoeben, Paul Steskens, Marc Stappers
Verantwoordelijke(n)
Bart Ankersmit (auteur)
Gerrit Engberts (auteur)
Wim Hoeben (auteur)
Paul Steskens (auteur)
Marc Stappers (auteur)
Bron ICOM-CC 21st Triennial Conference : preprints cultural connections in conservation, Oslo, 14–18 September 2026 (2026), pagina's 1006-1012
Illustratiesillustraties
Materiaalartikel
SamenvattingThe Collection Centre Netherlands (CC NL) exemplifies energy-efficient museum storage through innovative climate management and sustainable design. This 19,000 m² facility houses collections from four major Dutch institutions, with
carefully planned zoning into office, mixed-use, and storage areas. Airtight construction, high insulation levels, and activated thermal mass provide climate stability, while continuous monitoring enables detailed analysis of energy
consumption. The use of a cooling coil for dehumidification led to the decision to maintain a minimal indoor temperature of 17°C to dry the moisture-laden concrete. Optimization measures, such as CO₂-based ventilation and reduced operating hours, achieved a 21% reduction in annual energy use between 2021 and 2024. Strikingly, the smaller mixed zone accounted for most of the heating and cooling demand, while energy consumption in the larger storage zone was far less. In 2024, solar panels supplied 54% of the facility’s electricity, supported by energy storage. The CC NL illustrates how targeted optimization can ensure collection safety while providing significant energy savings.
carefully planned zoning into office, mixed-use, and storage areas. Airtight construction, high insulation levels, and activated thermal mass provide climate stability, while continuous monitoring enables detailed analysis of energy
consumption. The use of a cooling coil for dehumidification led to the decision to maintain a minimal indoor temperature of 17°C to dry the moisture-laden concrete. Optimization measures, such as CO₂-based ventilation and reduced operating hours, achieved a 21% reduction in annual energy use between 2021 and 2024. Strikingly, the smaller mixed zone accounted for most of the heating and cooling demand, while energy consumption in the larger storage zone was far less. In 2024, solar panels supplied 54% of the facility’s electricity, supported by energy storage. The CC NL illustrates how targeted optimization can ensure collection safety while providing significant energy savings.
AnnotatieMet literatuuropgave
Trefwoordendepots, klimaatbeheersing, binnenklimaat